(→Device Configuration) |
m |
||
Line 33: | Line 33: | ||
=Device Configuration= | =Device Configuration= | ||
− | The AlarmDecoder configuration viewed or modified in one of two ways: [[#Prompted|prompted]] or [[#Programatically|programmatically]]. | + | The AlarmDecoder configuration can be viewed or modified in one of two ways: [[#Prompted|prompted]] or [[#Programatically|programmatically]]. |
{| align="center" class="wikitable" border="1" | {| align="center" class="wikitable" border="1" |
Revision as of 13:10, 17 December 2013
Contents |
Commands
Command | Description |
---|---|
= | Reboot the device. |
! | Configure the device via prompts. |
C | Sets or retrieves configuration parameters. |
L | Emulate virtual zone opens and closes. |
\x01\x01\x01 | Send Function Key #1 |
\x02\x02\x02 | Send Function Key #2 |
\x03\x03\x03 | Send Function Key #3 |
\x04\x04\x04 | Send Function Key #4 |
0123456789*# | Send key to panel |
Device Configuration
The AlarmDecoder configuration can be viewed or modified in one of two ways: prompted or programmatically.
Name | Default Value | Valid Values (Regex) | Description |
---|---|---|---|
ADDRESS | 18 | [0-9]{2} | Keypad address assigned to the AlarmDecoder. |
CONFIGBITS | FF00 | [0-9a-f]{4} | Special settings for the device. See CONFIGBITS for more information. |
MASK | FFFFFFFF | [0-9a-f]{8} | Address mask used to filter for keypad alphanumeric messages. |
EXP | NNNNN | [YN]{5} | Emulation of zone expanders 1-5 |
REL | NNNNN | [YN]{4} | Emulation of relay expanders 1-4 |
LRR | N | [YN] | Emulation of Long Range Radio expander |
DEDUPLICATE | N | [YN] | If enabled, removes duplicate alphanumeric keypad messages. |
Prompted
If you send ! followed by a carriage return you will be prompted for each field. This prompt also includes a basic description of the setting as well as it's current value.
You may hit enter to keep the current value or enter a new one.
Example:
!>Ademco/DSC Mode A/D (A) :> !>Keypad Address (18) :> !WARNING. Do not enable a module if the physical module exists on the system. !Zone Expanders Y/N Max allowed: 02 !>expander module #01 ZN 09-16 (N) :> !>expander module #02 ZN 17-24 (N) :> !>expander module #03 ZN 25-32 (N) :> !>expander module #04 ZN 33-40 (N) :> !>expander module #05 ZN 41-48 (Y) :> !Relay Modules Y/N Max allowed: 04 !>relay module #01 (Y) :> !>relay module #02 (N) :> !>relay module #03 (N) :> !>relay module #04 (N) :> !>Emulate Long Range Radio Y/N: (Y) :> !>ZoneTracker track zone restore Y/N: (N) :> !>Address Filter Mask (ffffffff) :> !>Deduplicate (N) :> !>Config Bits (ff04) :>
Programmatically
You may retrieve all of the devices settings by sending C to the panel followed by a carriage return (\r).
Retrieving AlarmDecoder settings:
- Send: C\r
- Response: !CONFIG>ADDRESS=18&CONFIGBITS=ff00&LRR=N&EXP=NNNNN&REL=NNNN&MASK=ffffffff&DEDUPLICATE=N
It can also be used to set values:
- Send: CADDRESS=20\r
- Response: !>ADDRESS=20
The same command may be used to set multiple values:
- Send: CADDRESS=20&DEDUPLICATE=Y\r
- Response: !>ADDRESS=20&DEDUPLICATE=Y
Message Types
There are several types of messages produced by the AlarmDecoder. These include: Keypad, Relay Expander, Zone Expander, RFX, LRR, and AUI.
Keypad
[001000010000--------],010,[f70700060010808c08020000],"ARMED ***STAY** ZONE BYPASSED " | |||
Bit field | Numeric code | Raw data | Alphanumeric Keypad Message |
---|---|---|---|
[001000010000--------] | 010 | [f70700060010808c08020000] | "ARMED ***STAY** ZONE BYPASSED " |
Zone Expander
!EXP:07,01,01 | |||
Header | Zone Expander Address | Expander Channel | Data |
---|---|---|---|
!EXP | 07 | 01 | 01 |
Relay Expander
!REL:12,01,01 | |||
Header | Relay Expander Address | Expander Channel | Data |
---|---|---|---|
!REL | 12 | 01 | 01 |
RFX
!RFX:0180036,80 | |||
Header | Serial Number | Data | |
---|---|---|---|
!RFX | 0180036 | 80 |
LRR
!LRR:012,1,ARM_STAY | |||
Header | Event Data | Partition | Event Type |
---|---|---|---|
!LRR | 012 | 1 | ARM_STAY |
AUI
TODO